No stress rentals! We help you to choose the equipment that you need, we expedite shipment, and follow up.
Resistance measurement | |
Test Currents | Up to 30A and 7.5A Simultaneously and User Adjustable |
Charging voltage | Up to 100V |
Resistance range | Up to 100kΩ |
Accuracy | Up to 0.1% ± 0.1μΩ |
Turns Ratio Measurement | |
Test Voltage | Up to 250VAC User adjustable |
Turns Ratio Range | 0.8 to 50,000 |
Accuracy | Up to 0.04% |
General Specifications | |
Absolute input voltages | 90-264 VAC at 47-63Hz |
Consumption power | Maximum 900 VA |
Output power | Maximum 600 W |
Test voltage user selectable (AC) | 10 to 250 VAC |
Max. test current (AC) | 1 A |
Test current user selectable (DC) | 50mA-30A and 25mA-7.5A simultaneously |
Max test voltage (DC) | 50VDC (100VDC with automatic booster) |
Standard Accessories | Cable bags Kelvin measuring cables, 8 X 10m Safety GND cable, 1 X 10m Power cord 2 paper rolls 2 fuses USB memory stick Instruction manual |
Display | 7in TFT Color LCD |
Input devices | Capacitive touch screen, support mouse and keyboard |
Interfaces | 3 USB 2.0 full speed (2 hosts, 1 device) and Ethernet |
Printer | Internal 1.9in thermal printer |
Operating temperature | -10°C (14°F) to +55° C (131°F) |
Storage temperature | -20°C ( -4°F) to +70°C (158°F) |
Degree of protection (closed door) | IP67, dust-tight and water immersion up to a 1-meter depth |
Size | L: 525 mm (20.7 in) W: 437 mm (17.2 in) H: 213 mm (8.4 in) |
Weight (instrument) | 16.5 kg (36.4 lbs.) |